These cables are designed for connecting photovoltaic system components inside and outside of buildings and equipment with high mechanical requirements and extreme weather conditions. This product type is TUV approved.
DIN EN 50618 (H1Z2Z2-K) (formerly PV-1F according to 2PfG 1169/08.2007)
Conductor : Stranded tinned copper conductor per DIN VDE 0295 and IEC 60228 Class 5.
Insulation : Electron beam cross-linked, halogen free and flame retardant compound.
Sheath : Electron beam cross-linked, halogen free and flame retardant compound, Black
Rated Voltage U0/U : 1/1 kV AC; 1.5/1.5 kV DC
Maximum Permitted DC Voltage : 1.8 kV DC (conductor/conductor, non earthed system, circuit not under load)
Insulation Resistance : 1000 MΩ-km
Spark Test : 6000 Vac (8400 Vdc)
Voltage Withstand : 6500 Vac for 5 min
Maximum Voltage : 1.2KV (AC), 1.8KV (DC)
Ambient Temperature : -40°C ~ +90°C
Maximum Temperature At Conductor : 120°C (20000h) according to IEC/EN 60216-1
Short Circuit Temperature : 200°C/5 sec
Thermal Endurance Test : According to EN 60216-2 (temperature index +120°C)
Damp-Heat Resistance : According to EN 50618, Table 2with 85% humidity(test acc. to EN 60068-2-78)
Minimum Bending Radius : 4×OD (fixed), 5×OD (flexing)
Dynamic Penetration : According to Acc. to EN 50618, Annex D, Meets requirements of EN 50618.
Notch Propagation : According to 2 PfG 1169/08.2007 Annex G
Tensile Strength and Elongation of Insulation and Jacket : 250°C
Anticipated period of use : 25 years
Ovality : ≤15%
Ozone Resistance : According to EN 60811-403(25℃,24h,(250 to 300) × 10−4%) ;Method B: EN 50396(40℃,72h,55%RH, (200 × 10−6%)
Weathering- UV Resistance( Resistance on sheath) : Tensile strength and elongation at break after 720h (360 Cycles) of exposure to UV lights (acc. to EN 50289-4-17, Method A According to HD 605/A1)
Ammoniac resistant
Very good resistance to oils and chemicals
High wear and robust, abrasion resistant
The cables are conform to the EC directives CE 2006/95/EC (Low voltage directive) and RoHS 2002/95/EC (Restriction of Hazardous Substances)
Flame retardant according to EN 50265-2-1, IEC 60332-1, VDE 0482-332-1-2, DIN EN 60332-1-2
Low smoke emission according to EN 61034-2 (Light Transmittance ≥60%)
Halogen free according to EN 50525-1, Annex B
Low corrosivity of gases according to EN 50267-2-2, IEC 60754-2
No. of Cores ×Nominal Cross Section | No. of Stranding | Nominal Conductor Diameter | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diamater | Nominal Weight |
---|---|---|---|---|---|---|
No. ×mm² | - | mm | mm | mm | mm | kg/km |
1×1.5 | 30/0.25 | 1.58 | 0.70 | 0.80 | 5.4 | 40 |
1×2.5 | 50/0.25 | 2.04 | 0.70 | 0.80 | 5.9 | 50 |
1×4.0 | 56/0.30 | 2.59 | 0.70 | 0.80 | 6.6 | 70 |
1×6.0 | 84/0.30 | 3.17 | 0.70 | 0.80 | 7.4 | 80 |
1×10 | 78/0.40 | 4.07 | 0.70 | 0.80 | 8.8 | 130 |
1×16 | 128/0.40 | 5.22 | 0.70 | 0.90 | 10.1 | 200 |
1×25 | 199/0.40 | 6.51 | 0.90 | 1.00 | 12.5 | 290 |
1×35 | 279/0.40 | 7.71 | 0.90 | 1.10 | 14.0 | 400 |
1×50 | 396/0.40 | 9.00 | 1.00 | 1.20 | 16.3 | 550 |
1×70 | 360/0.50 | 10.8 | 1.10 | 1.20 | 18.7 | 750 |
1×95 | 475/0.50 | 12.6 | 1.10 | 1.30 | 20.8 | 970 |
1×120 | 608/0.50 | 14.2 | 1.20 | 1.30 | 22.8 | 1220 |
1×150 | 756/0.50 | 15.8 | 1.40 | 1.40 | 25.5 | 1510 |
1×185 | 925/0.50 | 17.4 | 1.60 | 1.60 | 28.5 | 1850 |
1×240 | 1221/0.50 | 20.4 | 1.70 | 1.70 | 32.1 | 2400 |
Cross Section | AWG | Maximum Conductor Resistance at 20°C | Maximum insulation Resistance at 20°C | Maximum insulation Resistance at 90°C | Current Carrying Capacity | ||
---|---|---|---|---|---|---|---|
Single cable free in air | Single cable on surfaces | 2 loaded cables adjacent on surfaces | |||||
mm² | - | Ω | MΩ.km | MΩ.km | A | A | A |
1.5 | 16 | 13.7 | 859 | 0.859 | 30 | 29 | 24 |
2.5 | 14 | 8.21 | 691 | 0.691 | 41 | 39 | 33 |
4 | 12 | 5.09 | 579 | 0.579 | 55 | 52 | 44 |
6 | 10 | 3.39 | 499 | 0.499 | 70 | 67 | 57 |
10 | 8 | 1.95 | 424 | 0.424 | 98 | 93 | 79 |
16 | 6 | 1.24 | 342 | 0.342 | 132 | 125 | 107 |
25 | 4 | 0.795 | 339 | 0.339 | 176 | 167 | 142 |
35 | 2 | 0.565 | 287 | 0.287 | 218 | 207 | 176 |
50 | 1/0 | 0.393 | 268 | 0.268 | 276 | 262 | 221 |
70 | 2/0 | 0.277 | 247 | 0.247 | 347 | 330 | 278 |
95 | 3/0 | 0.210 | 220 | 0.220 | 416 | 395 | 333 |
120 | 4/0 | 0.164 | 211 | 0.211 | 488 | 464 | 390 |
150 | 300 kcmil | 0.132 | 206 | 0.206 | 566 | 538 | 453 |
185 | 350 kcmil | 0.108 | 200 | 0.200 | 644 | 612 | 515 |
240 | 450 kcmil | 0.082 | 198 | 0.198 | 775 | 736 | 620 |
Ambient Temperature °C | Conversion Factor |
---|---|
Up to 60 | 1.00 |
70 | 0.91 |
80 | 0.82 |
90 | 0.71 |
100 | 0.58 |
110 | 0.41 |
Reduction factor for accumulation according to IEC 60364-5-52, Table B.52-17